Issue:
Factory default settings define the range for 0-10V or 4-20mA to be from low speed (LSP) to high speed (HSP).
Product Line:
Altivar ATV61 / ATV71
Environment:
All
Cause:
Would like to maintain 0-10V = 0-60Hz with adjustable low speed setting.
Resolution:
Preference is for the scaling range to be 0-HSP.
In Menu 1.5 INPUTS / OUTPUTS CFG, change the Reference Template from Standard to Pedestal. This allows LSP adjustments without affecting the scale range.