Goals and Symptoms
Summary
This article explains the GPS:Arbiter time synchronization format. Any GPS receiver may be used as a time synchronization source as long as the receiver outputs the ASCII time string every second and has On Time Mark (OTM).
Facts and Changes
Keywords
GPS
Arbiter
Time Synchronization
Quality Bit
Causes and Fixes
During normal operation of a GPS time synching system, time signals are sent out once per second as an ASCII string containing the time. The ASCII time string for GPS:ARBITER and GPS:TRUETIME/DATUM is as follows:
<SOH>DDD:HH:MM:SSQ<CR><LF>
Response: <SOH>ddd:hh:mm:ssQ<CR><LF>
Format: <SOH> Hex 01 The start bit of the <SOH> character is transmitted on time.
Q Time quality indicator. May be represented by:
space Locked, maximum accuracy
. (ASCII 46) Error < 1 microsecond
* (ASCII 42) Error < 10 microseconds
# (ASCII 35) Error < 100 microseconds
? (ASCII 63) Error > 100 microseconds
More Information
Refer to the 'Arbiter MODEL 1092A/B/C MODEL 1093A/B/C SATELLITE-CONTROLLED CLOCK OPERATION MANUAL' (http://www.arbiter.com/ftp/manuals/1092_93_manual.pdf)
Опубликовано для: Schneider Electric Казахстан
Нужна помощь?
- Инструмент для подбора продукции- Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения. 
- Получить коммерческое предложение- Заполните заявку онлайн, и с вами свяжется наш эксперт. 
- Где купить?- Легко находите ближайшего к вам дистрибьютора Schneider Electric. 
- Центр поддержки- Находите ресурсы поддержки для всех ваших потребностей в одном месте.