How do you add more then one Alarm Group to the Alarm Banner or Alarm Summary in Vijeo Designer?
Issue:
How do you add more then one Alarm Group to the Alarm Banner or Alarm Summary in Vijeo Designer?
Product Line:
Vijeo Designer, HMI, alarms
Resolution:
In the Vijeo Designer Navigator right click on the Alarms and select "New Alarm Category"
Then add the Alarm Groups you want to display in the Alarm Banner or Alarm Summary,
Now Click OK
Go to your Alarm Summary Settings or Alarm Banner Settings by double clicking on the Alarm Object on your Panel.
Then Select the Alarm Category instead of the Alarm Group. Then Click OK
This Alarm Banner or Alarm Summary will now show the alarms from the Alarm Category you added to the Alarm display.