What causes an 'OL9-1600 Not logged in to controller' error in Concept?

Issue
When a connection is attempted using Concept, the above message is returned.

Product line
Concept Programming software

Resolution
This is typically a Modbus timeout error.

  • Verify that the transmit and receive buffers are set to High in the PC's COM1: port parameters.
  • Try to connect to the PLC in ASCII mode at 2400 baud rate.
  • Is the laptop running off a low battery?
  • If the PLC is a Momentum, look for a bent pin.
  • Are Allen Bradley drivers activated?
  • It may be necessary to jumper out the handshaking (DTR/DSR) in the cable. The modified pinouts are included in the attached files.
See attached files for reference.

Schneider Electric Казахстан

Вложения
Compact_momentum_RJ45_to_DB9.zip [35.44 KB]
DB9_To_DB9_Pinout.zip [14.47 KB]
Узнайте больше
Линейка:
Узнайте больше
Линейка:

Нужна помощь?

  • Инструмент для подбора продукции

    Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.

  • Получить коммерческое предложение

    Заполните заявку онлайн, и с вами свяжется наш эксперт.

  • Где купить?

    Легко находите ближайшего к вам дистрибьютора Schneider Electric.

  • Центр поддержки

    Находите ресурсы поддержки для всех ваших потребностей в одном месте.

  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings