Issue
This resolution specifies the current injected by the STBART0200 module into an RTD probe.
Product Line
Advantys STB
STBART0200
Environment
Resolution
- For PT100, Ni100, or CU10 the module injects a 1.25ma current.
- For PT1000 or Ni1000 the module injects a 0.25ma current.