Чем мы можем помочь сегодня?

Report Manager error: The attempt to connect to the report server failed. Check your connection information and that the report server is a compatible version.

Issue:

When accessing http://localhost/Reports_ION, the Report Manager opens but displays the following error:
The attempt to connect to the report server failed. Check your connection information and that the report server is a compatible version.

Product Line:

Power Monitoring Expert 9.0

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

SQL Server Reporting Services (SSRS)

Environment:

Report Manager (Reports_ION)
SQL Server Reporting Services configuration
RSWebApplication.config

Cause:

The Report Manager is not configured with a fully qualified Report Server URL. Instead, it references only a virtual directory, which prevents Report Manager from establishing a connection to the report server.

Resolution:

  1. Navigate to the RSWebApplication.config file. By default, it is located at:
    C:\Program Files\Microsoft SQL Server\MSSQL.2\Reporting Services\ReportManager\RSWebApplication.config
    (The MSSQL.x folder number may vary depending on the SQL instance.)
  2. Open RSWebApplication.config for editing (run the editor as Administrator).
  3. Locate the ReportServer configuration entries under the <UI> section.
  4. Update the configuration as follows:
    1. Set the ReportServerUrl value to the full URL, typically:
      http://localhost/ReportServer_ION
    2. Remove any value from ReportServerVirtualDirectory, leaving it empty.
  5. After the changes, the configuration should appear similar to the following:

reference

6. Save the file.

7. Recycle the Application Pool used by Report Manager in IIS Manager.
a. Recycling the Application Pool forces IIS to reload the updated configuration.

8. Refresh http://localhost/Reports_ION and confirm the Report Manager loads without error.

Recommendation:

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

PME Version History

Schneider Electric Казахстан

Узнайте больше

Узнайте больше

Нужна помощь?

Инструмент для подбора продукции

Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.

Получить коммерческое предложение

Заполните заявку онлайн, и с вами свяжется наш эксперт.

Где купить?

Легко находите ближайшего к вам дистрибьютора Schneider Electric.

Центр поддержки

Находите ресурсы поддержки для всех ваших потребностей в одном месте.