The 'event priority' of the VIP Event Log is set to 192 by default. Most control actions need this to be adjusted to a more useful level. For example the AND/OR Module requires an event priorty of 15 on transition actions. To record these changes in the event log follow this procedure:

  1. Load ION Designer and open the VIP
  2. Open the AND/OR Module setup registers
  3. Change the AN# EvLog Mode to Log-On
  4. Open the EventLogCtl 1 setup registers in the VIP
  5. Change the EL1 Cutoff to your desired Event priorty level (15 for this example)
  6. Choose File -> Send & Save then close Designer
  7. Open the Microsoft Services and restart the ION LogInserter Service.

This should allow the VIP events to show up in a Event Log Viewer object, or the Global Event Log viewer (with the appropriate viewing priority filter).



Last Revised: April 17, 2008
Applies To: ION Enterprise 5.0 / 5.5 / 5.6
Original Author: LS
Public
All content © 1992-2008 Schneider Electric

Legacy KB System (APS) Data: RESL191707 V1.0, Originally authored by KBAdPM on 04/18/2008, Last Edited by KBAdPM on 04/18/2008
Related ranges: ION Enterprise V5.6, ION Enterprise V5.5, ION Enterprise V5.0

Schneider Electric Казахстан

  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings