Is it possible to have a READ_REG or WRITE_REG function block bridge Ethernet to Modbus through a TSXETG100?

Yes. A READ_REG or WRITE_REG block can reach a serial Modbus device through a TSXETG100 gateway, using the block's ADDRFLD parameter to carry both the gateway's address and the target device's ID.

How it works:

ADDRFLD is a 5-word array (WordArr5). Its 5 words are split across two roles:

Word(s)Contents
Word 1 (high byte)Physical slot of the Ethernet module in the local rack
Word 1 (low byte)The target device's Local ID, as configured in the TSXETG100's Device List
Words 2–5 TSXETG100's IP address, one octet per word

Example: to reach a device with Local ID 5 through a TSXETG100 at IP 192.168.40.7, with the Ethernet module in slot 4:

  • Word 1 = 16#0405 (hex 04 = slot 4, hex 05 = Local ID 5)
  • Words 2–5 = 192, 168, 40, 7

Note : The low byte of word 1 is the device's Local ID as set up on the TSXETG100 itself (Setup > Device List, Slave mode) — not necessarily its real serial slave address. The gateway's Device List maps each Local ID to a Remote ID (the device's actual address on the serial line). Check the gateway's Device List to confirm which Local ID has been assigned to the device you're targeting


Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings