How to round up value when displaying data log in PME Vista
Issue:
The customer does not want accuracy higher than whole number values.
Product Line:
Power Monitoring Expert 7.2.2
Power Monitoring Expert 8.2
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024
Environment:
Vista Data Log Viewer
Web Applications Data Log Viewer
Cause:
Software rounds to the thousandth place.
Resolution:
Confirm that Show Toolbox is checked in Options in the top-left then right-click on the data log viewer that needs to be changed in Vista. Go to the Query tab and click Edit SQL ... Add a ROUND function to the queries, for example
SELECT timestamp
, "Vll ab mean"
, "Vll bc mean"
, "Vll ca mean"
becomes
SELECT timestamp
, ROUND("Vll ab mean", 0) AS "Vll ab mean"
, ROUND("Vll bc mean", 0) AS "Vll bc mean"
, ROUND("Vll ca mean", 0) AS "Vll ca mean"
Save the file. Double-click on the data log viewer and you should see the value is rounded up to the nearest integer.