Is it possible to measure the B phase current in a 3-Wire Delta system using a CM-2000 series meter?

Issue

CM-2000 is configured with a 3 CT setup on a 3-wire delta system, which is unsupported and may result in inaccurate measurements due to improper system type selection.

Product Line
CM-2000 Series Meters

Environment
Metering Installation and Configuration

Cause

End User has inquired about whether or not a CM2000 can measure B Phase Current in a 3-Wire Delta System.


Resolution
The CM-2000 does not support a 3 CT configuration for 3-Wire Delta systems. The B phase is calculated regardless of whether you use 2 CT's or 3 CT's on a CM-2000 connected to a 3-Wire Delta system.
The appropriate system type for a 3-Wire Delta system is type 30 which requires 2 PTs and 2 CTs. Documentation for the CM2000 meter can be found here.