How Can I Safely Simulate a Fault on an Altivar Drive to Test Redundant System Operation?
Resolution:
Recommended Methods:
Method 1: Output Phase Loss Simulation (Preferred)
This method creates a fault without risking damage to equipment.
- Power down the drive.
- Disconnect the motor leads from all three drive output terminals.
- Verify that Output Phase Loss monitoring is enabled on the drive
(parameter location varies by model — refer to the drive’s programming manual). - Issue a RUN command with the motor disconnected.
Result:
The drive will detect an output phase loss and generate a fault.
Common fault codes may include OPF, OPF2, EPHO, or similar, depending on the drive model.
Method 2: External Fault via Logic Input
- Assign an External Fault function to a logic input.
- Trigger the input using a momentary contact closure.
Result:
The drive will immediately fault, allowing you to confirm fault detection and system switchover behavior.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.