Issue:
Programming drive to follow the speed por in hand and auto modes.
Product Line:
M-flex, E-flex etc
Environment:
All
Cause:
They do not have a separate 4- 20mA speed signal for auto mode so they want to use the speed pot mounted on the enclosure in auto mode.
Resolution:
Programming changes as follows
Main menu
Set access level to Expert
Drives menu
Menu 1.6
Ref 1 - AI1
Ref 2 switching is channel 1 active
Menu 1.7
Ref switching LI3
Ref 1b switching is AI1