How does the ATV61/71 JOG function work when in 3-wire control?
Issue:
JOG function in ATV61/71 when in 3-wire control
Product Line:
Altivar 61 71
Environment:
All models
Cause:
Understanding of control logic
Resolution:
In 3-wire control, LI1 from the STOP contact is normally high to allow a run command. LI2 is from the START contact and runs when it goes high, even momentarily. When the JOG function is added to LIx and is active, the VFD will run only when LI2 is high and will stop if LI2 drops low. The JOG action results from LI2 going high and low. So the sequence is to have LI1 and LIx go high and then use LI2 for jogging.
The same logic applies to a reverse logic input, such as LI3.
JOG function in ATV61/71 when in 3-wire control
Product Line:
Altivar 61 71
Environment:
All models
Cause:
Understanding of control logic
Resolution:
In 3-wire control, LI1 from the STOP contact is normally high to allow a run command. LI2 is from the START contact and runs when it goes high, even momentarily. When the JOG function is added to LIx and is active, the VFD will run only when LI2 is high and will stop if LI2 drops low. The JOG action results from LI2 going high and low. So the sequence is to have LI1 and LIx go high and then use LI2 for jogging.
The same logic applies to a reverse logic input, such as LI3.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.