Чем мы можем помочь сегодня?

Why Won’t the S-Flex 212 Drive Start When Using Remote Start (Terminals 5–6)?

Article available in these languages:

  • Испанский

Resolution:

If the S-Flex 212 drive does not start when closing the remote start contact on terminals 5–6, check the following common causes:

Troubleshooting Steps:

  1. Verify Remote Mode is Active

    • Ensure the drive is in Remote mode.
    • The LOC (Local) LED should be off. Press the LOC/REM button if needed.
  2. Confirm Proper Control Mode and Wiring

    • Make sure the AFC/Bypass switch is set to AFC mode.
    • Verify terminals 5–6 have a dry contact completing the circuit.
    • Ensure the Lower Limit (LL) is set above 0 Hz if no analog speed reference (VIA/VIB) is used.
  3. Check Communication Card Settings (if installed)

    • If a communication card is present, confirm these parameters:
      • CNOD = 0 (Terminal control)
      • FNOD = 1 (VIA) or 2 (VIB)
      • F108 = 48 (Force local always active)
  4. Inspect Wiring Connections

    • Look for loose or incorrect wiring in the control circuit.
  5. Review External Interlocks

    • Check if an end-of-damper circuit or other interlock is preventing the start command.
  6. Consult the Installation Manual

    • Refer to the S-Flex 212 wiring diagrams (manual 30072-451-83B) for correct configuration.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Казахстан

Вложения
30072-451-83B.pdf [4.33 MB]
Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings