What will cause enclose units not to run the motor in AFC or in Bypass?
Issue:
Enclosed units not to running the motor in AFC or in Bypass.
Product Line:
SFLEX, EFLEX, MFLEX, CPD, MCC, Field Drive, Econoflex, 58M
Environment :
All Enclosed products with Bypass
Cause:
The motor will not run in AFC or in Bypass
Resolution :
1). Check supply fuse primary side of transformer.
2). Check fuse on the secondary side of the transformer
3). Verify the overload is not tripped, (trip and then reset)
4). Verify the AFC/OFF/Bypass switch is getting voltage
5). With factory drawing in hand check the HOA and the AFC/OFF/Bypass circuit.
Enclosed units not to running the motor in AFC or in Bypass.
Product Line:
SFLEX, EFLEX, MFLEX, CPD, MCC, Field Drive, Econoflex, 58M
Environment :
All Enclosed products with Bypass
Cause:
The motor will not run in AFC or in Bypass
Resolution :
1). Check supply fuse primary side of transformer.
2). Check fuse on the secondary side of the transformer
3). Verify the overload is not tripped, (trip and then reset)
4). Verify the AFC/OFF/Bypass switch is getting voltage
5). With factory drawing in hand check the HOA and the AFC/OFF/Bypass circuit.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Изделие:
Узнайте больше
Изделие:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.