Here is the snapshot of error you may see while opening the web page of NOR.

Error Snapshot

This is an error linked to enhanced security features on JAVA.
To solve this issue take below steps.
- Go to  JAVA control panel from windows control panel
- Set the security level to medium. Its available inside security tab as shown.

Security Level
- Also  use the Exception Site list feature in JAVA control panel to run the applications blocked by security settings. Adding the URL of the blocked application to the
Exception Site list allows it to run with some warnings.
Steps to Add URLs to the Exception Site list
-Go to the Java Control Panel (On Windows Click Start and then Configure Java)
-Click on the Security tab
-Click on the Edit Site List button
-Click Add in the Exception Site List window
-Click in the empty field under the Location field to enter the URL Example: http://www.example.com.

Exception List

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings