ATV61 and ATV71 VW3A1101 remote keypad does not allow any selections to be made when pushing the enter button.
Issue:
ATV61 and ATV71 VW3A1101 remote keypad does not allow any selections to be made when pushing the enter button.
Product Line:
Altivar ATV61 and ATV71 VW3A1101
Environment:
All
Cause:
Enter button does not appear to work.
Resolution:
Make sure the drive is not running first.
Try swapping out the HMI keypads
Check to see if the buttons on the face of the drive work.
Try mounting the remote HMI on the face of the drive to see if the enter button works.
Try swapping out the cables.
Try using the modbus Canopen port vs the hmi port.
ATV61 and ATV71 VW3A1101 remote keypad does not allow any selections to be made when pushing the enter button.
Product Line:
Altivar ATV61 and ATV71 VW3A1101
Environment:
All
Cause:
Enter button does not appear to work.
Resolution:
Make sure the drive is not running first.
Try swapping out the HMI keypads
Check to see if the buttons on the face of the drive work.
Try mounting the remote HMI on the face of the drive to see if the enter button works.
Try swapping out the cables.
Try using the modbus Canopen port vs the hmi port.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.