Чем мы можем помочь сегодня?
Do the TM3 analog input modules supply power to the inputs?
Issue:
Reading analog inputs on a TM3 module
Product line:
All TM3 analog input modules for all Products that can use the TM3 modules
Environment:
Exostruxure Machine Expert, So Machine Expert Basic, ( formally SoMachine and SoMachine Basic).
Cause:
Not able to read any analog inputs on card.
Resolution:
No the TM3 analog input modules need to have a loop supply or a self powered field device to power the input.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.