What is the AL05 code shown on the ATV212?
Issue:
Looking for the AL05 code shown on the ATV212.
Product Line:
ALTIVAR 212, ATV212
Environment:
All
Cause:
Troubleshooting
Resolution:
AL05 is the alarm code display in case of a signal loss on an analog input.
Example on VIA in 4-20mA
FMOD = VIA
[4-20 mA loss] F644 = freewheel
[Loss of VIA] F633 = 20% --> 20% on F633 is for 4mA.
Start the drive with VIA higher than 4mA
--> The drive run and goes to the speed given by VIA.
If VIA signal is loose (VIA less than 4mA)
--> AL05 is display showing the 4-20mA loss is detected.
--> Then Drive is stopped in freewheel
If AL05 is display on your product :
- check the signal level on VIA
- then check F633 is set correctly
There is nothing in manual on this code.
Looking for the AL05 code shown on the ATV212.
Product Line:
ALTIVAR 212, ATV212
Environment:
All
Cause:
Troubleshooting
Resolution:
AL05 is the alarm code display in case of a signal loss on an analog input.
Example on VIA in 4-20mA
FMOD = VIA
[4-20 mA loss] F644 = freewheel
[Loss of VIA] F633 = 20% --> 20% on F633 is for 4mA.
Start the drive with VIA higher than 4mA
--> The drive run and goes to the speed given by VIA.
If VIA signal is loose (VIA less than 4mA)
--> AL05 is display showing the 4-20mA loss is detected.
--> Then Drive is stopped in freewheel
If AL05 is display on your product :
- check the signal level on VIA
- then check F633 is set correctly
There is nothing in manual on this code.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.