Чем мы можем помочь сегодня?

What is the wiring diagram for the HMISCU Analog Inputs and Outputs?

Issue
Where can I find the wiring diagram for the Analog Inputs and Outputs on the HMISCU?

Product Line
Harmony HMISCU (Analog Models: HMISBC, HMISCU6B5, HMISCU8B5)

Environment
Physical HMI / PLC

Resolution
The diagram below shows the wiring diagram for the Analog Inputs and Output on the HMISCU:

Wiring Diagram

For more information about the HMISCU, please see the Harmony SCU HMI Controller, Hardware Guide (pdf link)
Web Link: Harmony SCU Controller - Hardware Guide

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings