What is the input voltage tolerance on the ATV61 and ATV71 series drives?
Issue:
Input voltage tolerance on the ATV61 and ATV71
Product Line:
Altivar 61 & 71
Environment:
All models, All serial numbers.
Cause:
Input voltage tolerance range needed.
Resolution:
For single phase input, part # ATV61H075M3 through ATV61HU75M3: 200 -15% to 240 +10%
For three phase input, part # ATV61H***M3 and ATV61H***M3X: 200 -15% to 240 +10%
For three phase input, part # ATV61****N4 and ATV61W***N4C: 380 -15% to 480 +10%
For three phase input, part # ATV61H***Y: 500 -15% to 690 +10%
For single phase input, part # ATV71H075M3 through ATV71HU75M3: 200 -15% to 240 +10%
For three phase input, part # ATV71H***M3 and ATV71H***M3X: 200 -15% to 240 +10%
For three phase input, part # ATV71****N4 and ATV71W***N4C: 380 -15% to 480 +10%
For three phase input, part # ATV71H***Y: 500 -15% to 690 +10%
Input voltage tolerance on the ATV61 and ATV71
Product Line:
Altivar 61 & 71
Environment:
All models, All serial numbers.
Cause:
Input voltage tolerance range needed.
Resolution:
For single phase input, part # ATV61H075M3 through ATV61HU75M3: 200 -15% to 240 +10%
For three phase input, part # ATV61H***M3 and ATV61H***M3X: 200 -15% to 240 +10%
For three phase input, part # ATV61****N4 and ATV61W***N4C: 380 -15% to 480 +10%
For three phase input, part # ATV61H***Y: 500 -15% to 690 +10%
For single phase input, part # ATV71H075M3 through ATV71HU75M3: 200 -15% to 240 +10%
For three phase input, part # ATV71H***M3 and ATV71H***M3X: 200 -15% to 240 +10%
For three phase input, part # ATV71****N4 and ATV71W***N4C: 380 -15% to 480 +10%
For three phase input, part # ATV71H***Y: 500 -15% to 690 +10%
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.