How do I use the ATV71 keypad to operate my motor?
Issue:
Using the ATV71 keypad to operate a motor.
Product Line:
ATV71
Environment:
All models and serial numbers
Cause:
None
Resolution:
In the ATV71: a function key will need to be assigned to toggle between Terminal (T) and Keypad (K).
1. From the MAIN MENU scroll to ACCESS LEVEL, press enter
2. Scroll down to "Expert", press enter
3. Press ESC back to the MAIN MENU
4. Enter on DRIVE MENU
5. Scroll down to menu 1.6 COMMAND, press enter
6. Scroll down to "F4 Key assignment", press enter
7. Scroll down to "T/K", press enter
, ATV71
Using the ATV71 keypad to operate a motor.
Product Line:
ATV71
Environment:
All models and serial numbers
Cause:
None
Resolution:
In the ATV71: a function key will need to be assigned to toggle between Terminal (T) and Keypad (K).
1. From the MAIN MENU scroll to ACCESS LEVEL, press enter
2. Scroll down to "Expert", press enter
3. Press ESC back to the MAIN MENU
4. Enter on DRIVE MENU
5. Scroll down to menu 1.6 COMMAND, press enter
6. Scroll down to "F4 Key assignment", press enter
7. Scroll down to "T/K", press enter
, ATV71
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.