Video: How do you remove the bottom cover on the ATV61 and ATV71?
Issue:
Removal of bottom cover on ATV61 and ATV71.
Product Line:
Altivar ATV61 and ATV71 LHP units only or under 90KW
Environment:
All
Cause:
They can not get the the bottom cover off to check the power terminals.
Resolution:
1st Turn off all power make sure the drive is not powered up and the DC bus is discharged before starting.
You will need to turn the set screw counter clockwise on the control terminal pod. Next use a flat head screw drive to pry the corners on each side the cover to see if you can work it loose. Then pull down cover to remove it.
This procedure is demonstrated in the video below:
Removal of bottom cover on ATV61 and ATV71.
Product Line:
Altivar ATV61 and ATV71 LHP units only or under 90KW
Environment:
All
Cause:
They can not get the the bottom cover off to check the power terminals.
Resolution:
1st Turn off all power make sure the drive is not powered up and the DC bus is discharged before starting.
You will need to turn the set screw counter clockwise on the control terminal pod. Next use a flat head screw drive to pry the corners on each side the cover to see if you can work it loose. Then pull down cover to remove it.
This procedure is demonstrated in the video below:
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.