Cannot assign located variable to the Unity Momentum IO
Issue
Cannot assign located variable to the Unity Momentum IO
Product Line
Unity Momentum 171CBU*****
Environment
Unity, Control Expert
Resolution
Located variables cannot be assigned to the Momentum IO as in Concept.
Typically, the hardware configuration information is stored in %KW words for the Unity PLC's. Due to the hardware
limitation, the use of %KW words is not allowed for the Momentum PLC. As a result, Unity is forced to use reserved
%MW words for the module configuration information. The %MW words used for the configuration are intentionally
locked out to prevent the user from changing the values. This also locks out the the use of a %MW assignment for the IO.
Cannot assign located variable to the Unity Momentum IO
Product Line
Unity Momentum 171CBU*****
Environment
Unity, Control Expert
Resolution
Located variables cannot be assigned to the Momentum IO as in Concept.
Typically, the hardware configuration information is stored in %KW words for the Unity PLC's. Due to the hardware
limitation, the use of %KW words is not allowed for the Momentum PLC. As a result, Unity is forced to use reserved
%MW words for the module configuration information. The %MW words used for the configuration are intentionally
locked out to prevent the user from changing the values. This also locks out the the use of a %MW assignment for the IO.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.