Why would a drive not stop when the run command is removed?
Issue:
The drive does not stop, when the run command is removed.
Product Line:
Altivar 61, Altivar 71, Altivar 312, Altivar 212, Altivar12, Altivar 32
Environment:
All serial numbers
Cause:
The VFD is not responding to the stop command.
Resolution:
1). Verify how the drive is receiving the stop command.
2). Verify if the drive is programmed to get the stop command from that source.
3). Verify the drive is not in local control.
4). Check if the run signal is jumpered/bypassed
5). Check to see if the motor is backfeeding voltage back into the drive.
The drive does not stop, when the run command is removed.
Product Line:
Altivar 61, Altivar 71, Altivar 312, Altivar 212, Altivar12, Altivar 32
Environment:
All serial numbers
Cause:
The VFD is not responding to the stop command.
Resolution:
1). Verify how the drive is receiving the stop command.
2). Verify if the drive is programmed to get the stop command from that source.
3). Verify the drive is not in local control.
4). Check if the run signal is jumpered/bypassed
5). Check to see if the motor is backfeeding voltage back into the drive.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.