What level of current flow triggers an SCF2 fault on an ATV61 or ATV71 series drive?
Issue:
What level of current flow triggers an SCF2 fault on an ATV61/ATV71?

Product Line:
ATV61 / ATV71 series

Environment:
All models, All serial numbers

Cause:
Information not available in current literature.

Resolution:

SCF2

Principal :
The drive is protected against impedance (slow) short circuit, phase to phase or phase to ground on the output of the drive.
When there is a impedant short circuit the drive trips in SCF2 and the fault relay opens

Detection time:
It’s a software detection (a few ms).  Output current sum > 25% of the rated current of the drive.

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:

Нужна помощь?

  • Инструмент для подбора продукции

    Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.

  • Получить коммерческое предложение

    Заполните заявку онлайн, и с вами свяжется наш эксперт.

  • Где купить?

    Легко находите ближайшего к вам дистрибьютора Schneider Electric.

  • Центр поддержки

    Находите ресурсы поддержки для всех ваших потребностей в одном месте.

  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings