Чем мы можем помочь сегодня?
What are the "watts losses" or heat dissipation ratings for the ATV660 series drives?
Issue:
Needs the "watts loss" or heat dissipation ratings for the ATV660 series drives.
Product Line:
ATV660 enclosed Altivar Process Drives
Environment:
All models, all serial numbers
Cause:
Customer was unable to find information in current literature.
Resolution:
This information can be found in the user manual for the ATV660 series drive, Doc NHA91297 .
See attached file.
Input and Output Current Ratings and Dissipated Heat, Normal Duty Operation
| Vac | Rating | Drive Rating | Full Load Input Current (A) | Full Load Output Current (A) | Full Load Bypass Current (A) | Typical Dissipated Power at Rated Load (W) | |
|---|---|---|---|---|---|---|---|
| hp | kW | ||||||
| 230 | 1 | 0.7 | U07 | 2.6 | 4.6 | 4.2 | 63 |
| 2 | 1.5 | U15 | 5 | 8 | 6.8 | 100 | |
| 3 | 2.2 | U22 | 7.2 | 11.2 | 9.6 | 138 | |
| 5 | 3 | U40 | 12.9 | 18.7 | 15.2 | 226 | |
| 7.5 | 5.5 | U55 | 17.1 | 25.4 | 22 | 289 | |
| 10 | 7.5 | U75 | 22.8 | 32.7 | 28 | 401 | |
| 15 | 11 | D11 | 32.9 | 46.8 | 42 | 651 | |
| 20 | 15 | D15 | 45.5 | 63.4 | 54 | 768 | |
| 25 | 18 | D18 | 54.5 | 78.4 | 68 | 860 | |
| 30 | 22 | D22 | 64.3 | 92.6 | 80 | 972 | |
| 40 | 30 | D30 | 88.6 | 123 | 104 | 1231 | |
| 50 | 37 | D37 | 107.8 | 149 | 130 | 1553 | |
| 60 | 45 | D45 | 130.4 | 175 | 154 | 1789 | |
| 208 | 1 | 0.7 | U07 | 3 | 4.6 | 4.6 | 69.93 |
| 2 | 1.5 | U15 | 5.9 | 8 | 7.5 | 111 | |
| 3 | 2.2 | U22 | 8.4 | 11.2 | 10.6 | 153.18 | |
| 5 | 3 | U40 | 15 | 18.7 | 16.7 | 250.86 | |
| 7.5 | 5.5 | U55 | 20 | 25.4 | 24.2 | 320.79 | |
| 10 | 7.5 | U75 | 27 | 32.7 | 30.8 | 445.11 | |
| 15 | 11 | D11 | 39 | 46.8 | 46.2 | 722.61 | |
| 20 | 15 | D15 | 53 | 63.4 | 59.4 | 852.48 | |
| 25 | 18 | D18 | 67 | 78.4 | 74.8 | 954.6 | |
| 30 | 22 | D22 | 76 | 92.6 | 88 | 1078.92 | |
| 40 | 30 | D30 | 105 | 123 | 114 | 1366.41 | |
| 460 | 1 | 0.7 | U07 | 1.3 | 2.2 | 2.1 | 60 |
| 2 | 1.5 | U15 | 2.6 | 4 | 3.4 | 84 | |
| 3 | 2.2 | U22 | 3.8 | 5.6 | 4.8 | 115 | |
| 5 | 3 | U40 | 6.7 | 9.3 | 7.6 | 173 | |
| 7.5 | 5.5 | U55 | 9.1 | 12.7 | 10 | 231 | |
| 10 | 7.5 | U75 | 11.9 | 16.5 | 14 | 272 | |
| 15 | 11 | D11 | 17 | 23.5 | 21 | 378 | |
| 20 | 15 | D15 | 23.3 | 31.7 | 27 | 515 | |
| 25 | 18 | D18 | 28.9 | 39.2 | 34 | 680 | |
| 30 | 22 | D22 | 34.4 | 46.3 | 40 | 739 | |
| 40 | 30 | D30 | 45.9 | 61.5 | 52 | 898 | |
| 50 | 37 | D37 | 57.3 | 74.5 | 65 | 1072 | |
| 60 | 45 | D45 | 69.1 | 88 | 77 | 1324 | |
| 75 | 55 | D55 | 84.2 | 106 | 96 | 1418 | |
| 100 | 75 | D75 | 112.7 | 145 | 124 | 1823 | |
| 125 | 90 | D90 | 135.8 | 173 | 156 | 2120 | |
| 150 | 110 | C11 | 195 | 211 | 180 | 2530 | |
| 200 | 130 | C13 | 232 | 250 | 240 | 3150 | |
| 250 | 160 | C16 | 277 | 302 | 302 | 4030 | |
| 300 | 200 | C20 | 349 | 370 | * | 4380 | |
| 400 | 250 | C25 | 432 | 477 | * | 5750 | |
| 500 | 310 | C31 | 538 | 590 | * | 7810 | |
| 600 | 400 | C40 | 681 | 730 | * | 9900 | |
| 700 | 500 | C50 | 846 | 900 | * | 13330 | |
| 900 | 630 | C63 | 1058 | 1140 | * | 16250 | |
Опубликовано для: Schneider Electric Казахстан
Вложения
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.