What are the recommended wire sizes for the Altivar 600 Process Drive?
Issue:
Recommended wire sizes for the Altivar 600 Process Drive
Product Line:
Altivar 600
Environment:
All serial number
Cause:
Wire size
Resolution:
You would normally size the wire according to NEC and use a rating of 125% of the input line current for the rated drive. See below for the wire size recommendation based on Frame size.
https://www.se.com/us/en/download/document/EAV64301/
Recommended wire sizes for the Altivar 600 Process Drive
Product Line:
Altivar 600
Environment:
All serial number
Cause:
Wire size
Resolution:
You would normally size the wire according to NEC and use a rating of 125% of the input line current for the rated drive. See below for the wire size recommendation based on Frame size.
https://www.se.com/us/en/download/document/EAV64301/