How to autoload the Recipes from a RecipeSelect object in Vijeo Designer?

Issue:
Is it possible to autoload Recipes in Vijeo Designer?

Product Line:
Vijeo Designer (all versions)

Resolution:
It is possible to program a recipe to autoload in Vijeo Designer. In the RecipeSelect object properties, there is an option called AutoLoadRecipe. If set to TRUE, the recipe ingredient values will load automatically when the recipe name is selected at runtime.
recipe auto select

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.