What could have cause the error runtime mismatch when downloading to the Magelis HMI with Vijeo Designer?

Article available in these languages: Испанский

Issue:
What could have cause the error runtime mismatch when downloading to the Magelis HMI with Vijeo Designer?

Product Line:
Vijeo Designer

Resolution:
The error means that the Vijeo Designer development software version is not equal to the runtime version on the Magelis target.  Find out the version of the runtime on the Magelis and upgrade Vijeo Designer to that version or higher.

In the case where you cannot upgrade your Vijeo Designer to a higher version, we can downgrade the HMI's runtime by downloading via USB Memory Stick or SD Card (where applicable). Please see how to do so with this FAQ:
https://www.se.com/ww/en/faqs/FA199001/

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings