Power manager Integration Utility - When this utility is run, the error message "Export complete with errors. Please check logs for details" is seen
Cause
Running the Power Manager Integration utility with Windows user account instead of Administrator account
Log:
Resolution:
Run the tool with Administrator permissions.
Running the Power Manager Integration utility with Windows user account instead of Administrator account
Log:
2016-10-12 15:09:33 - ERROR: System.Security.SecurityException: Requested
registry access is not allowed.
at System.ThrowHelper.ThrowSecurityException(ExceptionResource resource)
at Microsoft.Win32.RegistryKey.OpenSubKey(String name, Boolean writable)
at
IntegrationUtility.Services.ProductRegistry.GetProductRegistryValue(String
subkey, String valueName)
The Zone of the assembly that failed was:
MyComputer
2016-10-12 15:10:19 - ERROR: Error enabling EWS: Exception is:
System.InvalidOperationException: Failed to map the path '/ews'.
at System.Web.Configuration.ProcessHostConfigUtils.MapPathActual(String
siteName, VirtualPath path)
at System.Web.Configuration.ProcessHostMapPath.MapPathCaching(String
siteID, VirtualPath path)
at
System.Web.Configuration.ProcessHostMapPath.System.Web.Configuration.IConfigMapPath2.MapPath(String
siteID, VirtualPath path)
at
System.Web.Configuration.WebConfigurationHost.InitForConfiguration(String&
locationSubPath, String& configPath, String& locationConfigPath,
IInternalConfigRoot configRoot, Object[] hostInitConfigurationParams)
at System.Configuration.Configuration..ctor(String locationSubPath, Type
typeConfigHost, Object[] hostInitConfigurationParams)
at
System.Configuration.Internal.InternalConfigConfigurationFactory.System.Configuration.Internal.IInternalConfigConfigurationFactory.Create(Type
typeConfigHost, Object[] hostInitConfigurationParams)
at
System.Web.Configuration.WebConfigurationHost.OpenConfiguration(WebLevel
webLevel, ConfigurationFileMap fileMap, VirtualPath path, String site,
String locationSubPath, String server, String userName, String password,
IntPtr tokenHandle)
at
IntegrationUtility.Services.ConfigurationProcessor.SetWebConfigurationValue(String
virtualPath, String key, String value)
at IntegrationUtility.Services.ConfigurationProcessor.EnableEws().
2016-10-12 15:10:19 - ERROR: Error enabling token service: Exception is:
System.InvalidOperationException: Failed to map the path
'/systemdataservice'.
at System.Web.Configuration.ProcessHostConfigUtils.MapPathActual(String
siteName, VirtualPath path)
at System.Web.Configuration.ProcessHostMapPath.MapPathCaching(String
siteID, VirtualPath path)
at
System.Web.Configuration.ProcessHostMapPath.System.Web.Configuration.IConfigMapPath2.MapPath(String
siteID, VirtualPath path)
at
System.Web.Configuration.WebConfigurationHost.InitForConfiguration(String&
locationSubPath, String& configPath, String& locationConfigPath,
IInternalConfigRoot configRoot, Object[] hostInitConfigurationParams)
at System.Configuration.Configuration..ctor(String locationSubPath, Type
typeConfigHost, Object[] hostInitConfigurationParams)
at
System.Configuration.Internal.InternalConfigConfigurationFactory.System.Configuration.Internal.IInternalConfigConfigurationFactory.Create(Type
typeConfigHost, Object[] hostInitConfigurationParams)
at
System.Web.Configuration.WebConfigurationHost.OpenConfiguration(WebLevel
webLevel, ConfigurationFileMap fileMap, VirtualPath path, String site,
String locationSubPath, String server, String userName, String password,
IntPtr tokenHandle)
at
IntegrationUtility.Services.ConfigurationProcessor.SetWebConfigurationValue(String
virtualPath, String key, String value)
at
IntegrationUtility.Services.ConfigurationProcessor.EnableTokenService().
Resolution:
Run the tool with Administrator permissions.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.