ATV630 series drives, How do I bring the total input impedance up to 5%? The drive catalog shows 3% internal impedance already, do we add a 2% reactor?
Issue:
The ATV630 series drives have 3% impedance standard, is there a way to bring that up to 5%?
Product Line:
ATV600 series process drives.
Environment:
All models, All serial numbers
Cause:
Information unavailable in current literature.
Resolution:
In order to bring the equivalent input impedance of the ATV600 series drives to 5%, add a 3% line reactor ahead of the drive, not 2%. The input impedance is not linear so a 2% reactor added to the 3% internal equivalent impedance will not yield 5% input impedance.
The ATV630 series drives have 3% impedance standard, is there a way to bring that up to 5%?
Product Line:
ATV600 series process drives.
Environment:
All models, All serial numbers
Cause:
Information unavailable in current literature.
Resolution:
In order to bring the equivalent input impedance of the ATV600 series drives to 5%, add a 3% line reactor ahead of the drive, not 2%. The input impedance is not linear so a 2% reactor added to the 3% internal equivalent impedance will not yield 5% input impedance.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.