Issue:
Is there a recommendation for the maximum motor cable length for ATV660 drives?
Product line:
Altivar ATV660
Environment:
All
Cause:
N/A
Resolution:
150 meters with shielded cable
250 meters with unshielded cable
300 meters with shielded cable and option "300m DV/DT filter"
500 meters with unshielded cable and option "300m DV/DT filter"