How many Unary alarms are available in PM2200 energy meter ?

Issue

How many unary alarms are available in the PM2200 energy meter?

Product Line

PowerLogic™ PM2200 Series Meter.

Environment

Energy monitoring and diagnostics in electrical distribution systems where alarm notifications are required for operational awareness and troubleshooting.

Resolution

The PM2200 meter includes a set of 4 unary alarms, each designed to indicate specific operational or diagnostic conditions.


Unary Alarms Overview

Alarm LabelDescription
Meter Power UpIndicates the meter has powered on after losing control power.
Meter ResetIndicates the meter has reset for any reason.
Meter DiagnosticIndicates the meter’s self-diagnostic feature has detected a problem.
Phase ReversalIndicates the meter has detected a phase rotation different than expected.