Can I import a StruxureWare DCE VM backup into a hardware server?
Issue:
Can not import a StruxureWare DCE VM backup into a hardware server.
Product Line:
StruxureWare Data Center Expert.
Environment:
StruxureWare Data Center Expert 7.x VM
Hardware servers AP9465, AP9470, AP9475
Cause:
In versions of DCE prior to 7.2.4, it was possible to back up a VM server and import that backup to a hardware server. There were issues that may occur when this was done but for the most part, it would work.
Since 7.2.4 however, the restore of a VM backup to a hardware server does not work.
Resolution:
Importing a VM backup to a hardware server was never totally supported and the system was not designed to be used in that manner. You can take a hardware backup and assuming you've provided the proper resources for hard drive space and a second NIC, import that hardware backup into a DCE VM.
Can not import a StruxureWare DCE VM backup into a hardware server.
Product Line:
StruxureWare Data Center Expert.
Environment:
StruxureWare Data Center Expert 7.x VM
Hardware servers AP9465, AP9470, AP9475
Cause:
In versions of DCE prior to 7.2.4, it was possible to back up a VM server and import that backup to a hardware server. There were issues that may occur when this was done but for the most part, it would work.
Since 7.2.4 however, the restore of a VM backup to a hardware server does not work.
Resolution:
Importing a VM backup to a hardware server was never totally supported and the system was not designed to be used in that manner. You can take a hardware backup and assuming you've provided the proper resources for hard drive space and a second NIC, import that hardware backup into a DCE VM.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.