Чем мы можем помочь сегодня?
PME - Too many registers exposed in Micrologic X driver to EWS
Issue
In PME8.2 and previous versions
1. Too many registers exposed in Micrologic X driver (in this file only 66 measurements have been exposed similar to legacy Micrologic drivers)
2. IONReferenceName and MeasurementName attributes and not aligned MM_MeasurementMap and PDM labels respectively
Environment
EWS service
Resolution
1. Replace the Types.Measurements_MicrologicX file in C:\Program Files(x86)\Schneider Electric\Power Monitoring Expert\system\WebServices\Extensions
2. Update the EWS server in Management console
In PME8.2 and previous versions
1. Too many registers exposed in Micrologic X driver (in this file only 66 measurements have been exposed similar to legacy Micrologic drivers)
2. IONReferenceName and MeasurementName attributes and not aligned MM_MeasurementMap and PDM labels respectively
Environment
EWS service
Resolution
1. Replace the Types.Measurements_MicrologicX file in C:\Program Files(x86)\Schneider Electric\Power Monitoring Expert\system\WebServices\Extensions
2. Update the EWS server in Management console
Опубликовано для: Schneider Electric Казахстан
Вложения
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.