Issue:
What driver to use in Vijeo Designer to communicate to Allen Bradley Drive over Ethernet/IP?
Product Line:
EIP, Magelis
Resolution:
Due to Vijeo Designer Rockwell EIP driver are specific to a controller type. It is not possible to use that driver. To communicate to any third party devices (including a AB drive) over Ethernet/IP, it is recommended to use the Ethernet/IP Explicit driver under Generic Drivers.
What driver to use in Vijeo Designer to communicate to Allen Bradley Drive over Ethernet/IP?
Product Line:
EIP, Magelis
Resolution:
Due to Vijeo Designer Rockwell EIP driver are specific to a controller type. It is not possible to use that driver. To communicate to any third party devices (including a AB drive) over Ethernet/IP, it is recommended to use the Ethernet/IP Explicit driver under Generic Drivers.