Чем мы можем помочь сегодня?
Video: How to configure PowerChute Network Shutdown to start the shutdown process once the UPS has been running on battery for a specified time?
Issue:
Would like PowerChute Network Shutdown to begin the shutdown process once the UPS has run on battery for pre-determined amount of time.
Product Line:
PowerChute Network Shutdown
Environment:
All supported OS
Cause:
UPS on battery
Resolution:
- Log into PowerChute web interface by entering the systems IP address or FQDN on port 6547. Examples https://192.168.1.10:6547 or https://MYComputer@myOffice.com:6547
- Go to Configure Events
- Select UPS On Battery and click Shutdown
- Click Enable Shutdown
- Enter the desired amount of time you would like the UPS to run on battery prior to PowerChute starting the shutdown process and then click Apply.
For assistance installing PowerChute Network Shutdown see
How to install PowerChute Network Shutdown v5.1 onto Windows OS.
How to install, deploy, and configure PowerChute Network Shutdown version 5.x with VMware ESXi 7.x or above managed by vCenter Server 7.x or above.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.