Video: Sites/Devices cannot be connected in Power Monitoring Expert
Issue
Some sites and or devices cannot connect in PME. The IP addresses are unable to be pinged as well, but Modbus Tester or ION Setup can communicate successfully.
Product Line
PME7.x
PME8.x
PME 9.0, PME2020, PME2021, PME2022, PME2023
Environment
Device / site communications
Cause
Customers may block the Ping command through the network for security reasons. If Ping is blocked, and 'ICMP Timeout' is configured (in Advanced Properties of Site or Device configuration), this will cause them to not connect.
Resolution
Open the Advanced Properties section of the site or device by right clicking in the white space and change the 'ICMP Timeout' setting to 0, which is also the default value.
Some sites and or devices cannot connect in PME. The IP addresses are unable to be pinged as well, but Modbus Tester or ION Setup can communicate successfully.
Product Line
PME7.x
PME8.x
PME 9.0, PME2020, PME2021, PME2022, PME2023
Environment
Device / site communications
Cause
Customers may block the Ping command through the network for security reasons. If Ping is blocked, and 'ICMP Timeout' is configured (in Advanced Properties of Site or Device configuration), this will cause them to not connect.
Resolution
Open the Advanced Properties section of the site or device by right clicking in the white space and change the 'ICMP Timeout' setting to 0, which is also the default value.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.