Why I have a popup error message “Operation unsuccessful” when I start the operation PC-to-controller download with SomachineBasicV5.1SP1 ?
Only with SoMachine Basic V5.1SP1 version  , when the application is protected by a password  , when we try to download an application from PC to M221 controller, we may have a popop error message "Operation unsuccesful" and then another popup message "could not receive reponse from controller"  in case the option "Reset memories" is not checked

In commissioning Tab, when connected to the M221 PLC, check the options download settings , and activate the option Reset memories ( see attached capture screen) in order to success to download

Schneider Electric Казахстан

Вложения
ResetMemories.jpg [110.02 KB]
Узнайте больше
Линейка:
Узнайте больше
Линейка:

Нужна помощь?

  • Инструмент для подбора продукции

    Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.

  • Получить коммерческое предложение

    Заполните заявку онлайн, и с вами свяжется наш эксперт.

  • Где купить?

    Легко находите ближайшего к вам дистрибьютора Schneider Electric.

  • Центр поддержки

    Находите ресурсы поддержки для всех ваших потребностей в одном месте.

  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings