How do we evaluate number of modifications in M580 HSBY
Issue:
How do we evaluate number of modifications in M580 HSBY?
Would every variable change or section change be taken account as 1 number of modifications.?
Product Line:
Modicon M580
Environment:
EcoStruxure Control Expert
Unity Pro
Resolution:
No.The number of modifications configured at Hot Standby tab of CPU is used to specify the maximum number of modifications allowed between Primary CPU & Standby CPU.
The number of modifications increase by 1 upon every build change (no matter how many variables or sections you had changed within the same time period)
How do we evaluate number of modifications in M580 HSBY?
Would every variable change or section change be taken account as 1 number of modifications.?
Product Line:
Modicon M580
Environment:
EcoStruxure Control Expert
Unity Pro
Resolution:
No.The number of modifications configured at Hot Standby tab of CPU is used to specify the maximum number of modifications allowed between Primary CPU & Standby CPU.
The number of modifications increase by 1 upon every build change (no matter how many variables or sections you had changed within the same time period)
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.