why don't my safety modules recover after a power cycle
most likely, the SAFE task is in stop after the power cycle. In order to run automatically the SAFE task on power cycle, the CPU setting "automatic start in run" must be checked

Basics :
A power cycle leads to a warm start. By design, the SAFE task cannot perform a "warm" start, but only a "cold" start. On power cycle, if the CPU setting "automatic start in run" is not checked, the MAST task will execute a warm start, therefore the safety task will not be able to proceed, and the user will have to switch the SAFE task to RUN manually using the "PLC screen" Task tab in maintenance mode.

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:

Нужна помощь?

  • Инструмент для подбора продукции

    Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.

  • Получить коммерческое предложение

    Заполните заявку онлайн, и с вами свяжется наш эксперт.

  • Где купить?

    Легко находите ближайшего к вам дистрибьютора Schneider Electric.

  • Центр поддержки

    Находите ресурсы поддержки для всех ваших потребностей в одном месте.

  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings