What do the different colors mean on the LED indicator for the Thermal Monitoring solution installed in the Model 6 Motor Control Center
An external single LED status indicator is provided on the unit disconnect mechanism for displaying thermal status conditions.
Solid Green - OK No Alarms No Color / Black - Not Operating / Loss of Power to Device
Solid Yellow - Phase Temperature Imbalance Flashing Yellow - Line / Load Delta Thermal
Flashing Red - High Temperature Solid Red - Sensor Failure Signal Loss
Temperature Alarms are configurable by dip switches.
The Thermal Monitoring solution includes Modbus RS485 serial communications capability. iMCC Network solutions with this feature are available under special order configurations.
For detailed installation and setup information reference the Exertherm instruction bulletin
For pricing and lead time information contact the Technical Assistance Group at the Seneca, SC manufacturing location.
Solid Green - OK No Alarms No Color / Black - Not Operating / Loss of Power to Device
Solid Yellow - Phase Temperature Imbalance Flashing Yellow - Line / Load Delta Thermal
Flashing Red - High Temperature Solid Red - Sensor Failure Signal Loss
Temperature Alarms are configurable by dip switches.
The Thermal Monitoring solution includes Modbus RS485 serial communications capability. iMCC Network solutions with this feature are available under special order configurations.
For detailed installation and setup information reference the Exertherm instruction bulletin
For pricing and lead time information contact the Technical Assistance Group at the Seneca, SC manufacturing location.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.