Чем мы можем помочь сегодня?
TeSys T Motor Management Controller, Z1, Z2 terminals connection in case an External Ground current transformer is not used
Issue:
If an external ground current transformer is not being used, is it necessary to connect anything to the Z1 and Z2 terminals of the LTMR?
Product Line:
Tesys T LTMR product line.
Environment:
All situations where an external ground current transformer is not being used.
Cause:
Clarification of product characteristics.
Resolution:
If external ground current transformer is not used, then nothing should be connected to terminals Z1, Z2 of LTMR.
If an external ground current transformer is not being used, is it necessary to connect anything to the Z1 and Z2 terminals of the LTMR?
Product Line:
Tesys T LTMR product line.
Environment:
All situations where an external ground current transformer is not being used.
Cause:
Clarification of product characteristics.
Resolution:
If external ground current transformer is not used, then nothing should be connected to terminals Z1, Z2 of LTMR.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.