PME 8.x: How to use the Web Viewer Gadget to display Real Time Trends

Issue
Setting up the web viewer gadget to display real-time trends.

Product Line
Power Monitoring Expert 8.x

Environment
Power Monitoring Expert
Web Applications

Cause
The user requires the setup of real-time trends in dashboards.

Resolution
1. Log into PME Web Applications by navigating to (http://[SERVERNAME]/web) or using (http://localhost/web) directly from the server.
2. Click on the 'Trends' tab, and select one of the trends set within the Trends Library.
3. Right-click on the selected 'Trend' and select 'Open in New Window'.
PME 8.x: How to use the Web Viewer Gadget to display Real Time Trends

4. Copy the unique URL generated for this trend from the browser's URL address bar.
PME 8.x: How to use the Web Viewer Gadget to display Real Time Trends
5. Navigate to the 'Dashboards' tab and click on 'Edit Dashboards' within the Dashboard Controls section.
6. Click on 'Add Gadget' and select the 'Web Viewer' gadget.
7. Define a 'Title' within the 'Gadget Setup - General Settings' window and click Next.
8. Paste the unique trend URL from the clipboard to the 'Source' field, and select the 'Refresh Interval' and 'Display' preferences.
9. Click 'Finish' to save the Web Viewer gadget configuration.

Gadget Setup

Schneider Electric Казахстан

Узнайте больше

Узнайте больше

Нужна помощь?

Инструмент для подбора продукции

Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.

Получить коммерческое предложение

Заполните заявку онлайн, и с вами свяжется наш эксперт.

Где купить?

Легко находите ближайшего к вам дистрибьютора Schneider Electric.

Центр поддержки

Находите ресурсы поддержки для всех ваших потребностей в одном месте.