Issue:
Causes of SCF4 fault on the ATV320 drive.
Product Line:
ATV320 drive
Environment:
All
Cause:
IGBT short circuit
Resolution:
SCF4 [IGBT short circuit] • Power component detected fault. • Contact Schneider Electric Product Support.
Troubleshooting check the motor and wiring to the motor.
Disconnect the motor turn off OPL and run the drive open circuit at 15 30 45 60hz
Running the Drive open circuit if the drive still fails then there is an issue with the drive.
Causes of SCF4 fault on the ATV320 drive.
Product Line:
ATV320 drive
Environment:
All
Cause:
IGBT short circuit
Resolution:
SCF4 [IGBT short circuit] • Power component detected fault. • Contact Schneider Electric Product Support.
Troubleshooting check the motor and wiring to the motor.
Disconnect the motor turn off OPL and run the drive open circuit at 15 30 45 60hz
Running the Drive open circuit if the drive still fails then there is an issue with the drive.
Опубликовано для: Schneider Electric Казахстан

