Altivar drive measures electrical power (from voltage and current) and considers the efficiency of the motor to give you result in form of mechanical power. Moreover, the power you enter in Altivar drive configuration , which is also shown on motor plate is the nominal mechanical power on motor shaft. Nominal electrical power is determined by rated U, rated I and cos phi.
So power vs flow curve reflects mechanical power on motor (pump) shaft. It is not hydraulic power. If you check the pump datasheet published by pump manufacturers, the declared power is the power (mechanical) consumed by the pump.
So power vs flow curve reflects mechanical power on motor (pump) shaft. It is not hydraulic power. If you check the pump datasheet published by pump manufacturers, the declared power is the power (mechanical) consumed by the pump.
Опубликовано для: Schneider Electric Казахстан


Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.