Issue:
Tesys T for overload protection on an ATS48.
Product Line:
ATS48
Environment:
All
Cause:
Customer had Tesys T optioned use in an ATS48.
Resolution:
No, The ATS48 controller is a UL Listed motor controller with integrated motor and controller thermal overload protection. The motor and controller temperature are continuously calculated based on the controller nominal current and the current that is actually drawn. Typically TeSys is only used with the ATS48 when Bypass is supplied and when the customer wants to monitor over communications other than Modbus RTU.
Tesys T for overload protection on an ATS48.
Product Line:
ATS48
Environment:
All
Cause:
Customer had Tesys T optioned use in an ATS48.
Resolution:
No, The ATS48 controller is a UL Listed motor controller with integrated motor and controller thermal overload protection. The motor and controller temperature are continuously calculated based on the controller nominal current and the current that is actually drawn. Typically TeSys is only used with the ATS48 when Bypass is supplied and when the customer wants to monitor over communications other than Modbus RTU.
Опубликовано для: Schneider Electric Казахстан



