Issue
Why is the gateway address not being displayed on M580 embedded web page?
Configuring the gateway as shown below: 10.130.2.254
The embedded M580 webpage is displaying the gateway address: 0.0.0.0
Product Line
M580, Unity pro , Control Expert
Resolution
This is issue is reported on M580 firmware below or equal to 2.20. The issue is no longer present in firmware above 2.20
Why is the gateway address not being displayed on M580 embedded web page?
Configuring the gateway as shown below: 10.130.2.254
The embedded M580 webpage is displaying the gateway address: 0.0.0.0
Product Line
M580, Unity pro , Control Expert
Resolution
This is issue is reported on M580 firmware below or equal to 2.20. The issue is no longer present in firmware above 2.20
Опубликовано для: Schneider Electric Казахстан



