Issue:
Adjustment to reduce motor oscillation in the ATS48.
Product Line:
ATS48
Environment:
All
Cause:
Motor is making a imbalance noise during start and stop.
Resolution:
Stator loss compensation 0 to 90% default 50%
Parameter active in acceleration phases (and deceleration phases if StY is set to -d-).
In the event of torque oscillations, reduce this parameter gradually until the device is functioning correctly.
Oscillations are most common if the soft starter is connected in motors with excessive slip.